Retrofit of Storm
Water Treatment Controls in a Highway Environment
Modification des systèmes existants de
traitement des eaux de ruissellement sur un réseau autoroutier
Scott Taylor Dr. Michael Barrett
RBF Consulting Center
for Research in Water Resources
P.O. Box 57057 University
of Texas
Irvine, CA USA 92619 Austin,
TX USA 78712
staylor@rbf.com mbarrett@mail.utexas.edu
RESUME
Un programme pilote, pour le contrôle du traitement des eaux de ruissellement, a été développé pour estimer les coûts et les bénéfices de l’adaptation au réseau routier des BMP (Best Management Practices) structurelles conventionnelles. Le côté unique de ce programme réside dans les trente neuf installations placées, conçues, construites, mises en œuvre et entretenues utilisant, sur une période de cinq ans, des critères cohérents et des protocoles de test et de suivi. Le budget de ce projet dépassa quinze millions de dollars US. Le concept de cette étude, pour évaluer les coûts (de construction, mise en œuvre, et maintenance) et les bénéfices (éléments présents et leur diminution au travers de BMP), était basé sur la construction de prototypes d’appareils de mesure sur des sites du réseau de transport de la Californie du sud (Caltrans). La purification estimée par ces appareils a généralement été en accord avec les résultats d’autres études. Néanmoins, certains de ces appareils ont montré que les concentrations d’éléments en sortie étaient indépendantes des concentrations d’éléments à l’entrée. Ceci nécessita le développement d’une méthode alternative pour l’évaluation de l’efficacité de la purification. Les paramètres généralement acceptés des concepts de BMP ont été ajustés, et des stratégies concernant le contrôle de vecteur ont été développées.
ABSTRACT
A storm water
treatment control pilot program was developed to assess the costs and benefits
of retrofitting conventional structural Best Management Practices (BMPs) into
highway infrastructure. The program was
unique in that thirty-nine installations were sited, designed, constructed,
operated, and maintained using consistent criteria, monitoring and testing
protocols over a five-year period. The
project budget exceeded $15 million US dollars. Constituent removal of the devices was found to be generally
consistent with that reported by other studies; however, some of the devices
exhibited constituent effluent concentrations that were independent of the
influent concentration, necessitating the development of an alternate method
for evaluating removal efficiency.
Refinements in generally accepted BMP design parameters were determined,
and strategies for vector control were also developed.
KEYWORDS
best management
practices, highway runoff, stormwater treatment, sustainable drainage systems
The BMP Retrofit Pilot Program was implemented to determine the costs
and benefits of retrofitting highway infrastructure, facility maintenance
stations (corporation yards) and park and ride lots with conventional
structural Best Management Practices (BMPs).
The program was developed to record costs (construction, operation and
maintenance) and constituent removal by constructing field-scale devices at
selected locations in the California Department of Transportation (Caltrans)
system. The devices shown in Table 1
were studied as a part of this program:
Table 1. Device Types
and Number of Installations
Device
|
Number of Sites |
Device |
Number of Sites |
|
Extended Detention Basin |
5 |
Biofilter Strip |
3 |
|
Infiltration Basin |
2 |
Infiltration Trench |
2 |
|
Wet Basin |
1 |
Drain Inlet Insert |
6 |
|
Sand Media Filter |
8 |
CDS** |
2 |
|
MCTT* |
3 |
Oil/Water Separator |
1 |
|
Biofilter Swale |
6 |
Perlite/Zeolite Filter |
1 |
* Multi-Chambered Treatment Train
** Continuous Deflective Separation
The study was
unique in that thirty-nine BMPs were investigated using identical protocols for
constituent removal. Paired
flow-weighted samples were collected from 26 BMP sites and grab samples were
collected from an additional 11 sites.
In all, over 13,400 chemical analyses were performed on paired samples
collected during three consecutive rainy seasons. Consequently, this study is thought to be the most comprehensive
investigation of conventional structural BMP performance completed to date.
Study sites were selected in two Caltrans southern California Districts
using a weighted decision matrix process. Criteria important in the selection
of the site for each BMP were listed, and each criterion was then assigned a
weighting factor. Further, the order of site selection was also considered to ensure
that the devices with the most restrictive criteria were located first,
followed by devices with less restrictive criteria in descending order.
Infiltration sites generally had the most restrictive siting criteria (space
and soil requirements).
The BMPs were monitored to determine their effectiveness at removing a
number of conventional constituents commonly observed in highway runoff. With the exception of the drain inlet
insert, oil-water separator and infiltration BMPs, all the sites were outfitted
with automatic samplers (Sigma 900 Max Series) and flow meters (Sigma 950
Series) to collect flow weighted composite samples of the influent and effluent
of the devices. Automatic samplers
consisted of a peristaltic pump, pump control electronics, a sample
distribution system, a power supply, and a housing that contained the composite
bottle(s). Rain gauges (Sigma 2149)
were installed at all sites. A typical
monitoring configuration is shown in Figure 1.


Figure 1 – Typical
Monitoring Configuration
Each of the BMPs
was designed using conventional criteria found in contemporary publications
such as Young et al. (1996) and WEF (1998).
Although the study was not specifically designed to evaluate the effects
of discrete BMP design parameters, there were a sufficient number of
installations for most devices to make some assessments in this regard.
The basic design criteria for detention basins included detention time,
length/width ratio, and depth. Basins
were designed for a water quality volume drawdown time of 72 hours, with the
objective of providing an average detention time of 24 hours for all storms up
to the water quality design storm (a storm with a recurrence interval of about
1 year). This was accomplished by
providing a staged riser-type outlet configuration. A minimum length to width ratio of 3:1 was used and the depth of
maintained between 0.5 and 1.2 meters to prevent resuspension of material.
Five basins were constructed with length to width ratios from 3:1 and
exceeding 10:1. TSS removal performance
did not vary significantly with the length to width ratio. It can be concluded that exceeding a length
to width ratio of 3:1 will not enhance removal performance, and it is the author’s
opinions from field observation that lower ratios would not significantly
impair performance. It was noted in the
field that the basins filled rapidly (on average within 3 hours from the start
of rainfall) but had an average residence time of about 18 hours. This effectively precludes an idealized Type
II sedimentation process where the influent moves through the basin in a plug
flow fashion in favor of a more classic application of Stokes Law and vertical
settling. Relaxing length to width
criteria to less than 2:1 may be acceptable with little performance penalty.
A more critical
element was the re-suspension of particulates near the basin inlet structure
that was observed at several locations, underscoring the need to provide
effective energy dissipation where the inflow jet enters the basin. Another interesting finding was the
discrepancy between calculated and actual draw down times noted at some of the
locations. Orifices in the outlet
risers were relatively small (about 3 cm), which, coupled with the inherent
error in estimating the orifice coefficient tended to underestimate the actual
discharge. This problem was compounded
by flow discharging through boltholes in the outlet structure. It is recommended that draw down times are
field-verified for a variety of basin stages and post-construction
modifications to the orifice size made as appropriate.
Two other findings
observed during maintenance of the basins are noteworthy. At one of the pilot locations that exhibited
a consistent wind direction, floating trash and debris tended to accumulate at
the lee side of the basin. This
observation can be used to advantage for locations with a prevailing wind
direction by locating a maintenance ramp where the trash will accumulate and
keeping the basin outlet at the extreme upwind location away from floating
debris. During the course of the
three-year study, sediment accumulated at a rate of less than 1% by volume per
year. This would indicate a required
clean-out frequency in excess of once every 10 years.
Sand filters were designed using standards developed by the City of
Austin, Texas, specifically for storm water use. The design sedimentation chamber draw down time was 24 hours, and
the assumed permeability of the sand was 1.07 m/d. The sedimentation chamber was drained through a perforated riser;
the rate of discharge from the riser was controlled via an orifice plate in the
barrel.
Observation of the filters during rain events and maintenance during the
study period afforded several recommendations for future designs. It was noted that the level spreader used to
distribute effluent from the sedimentation chamber over the sand bed was
ineffective. The flow from the sediment
chamber was small (on average about 0.01m/s) and with relatively large weirs
(greater than 3 meters) resulting in flow only over isolated sections of the
weir that varied marginally from the specified grade. Flow subsequently pooled over small portions of the sand bed, again
in areas with the lowest elevation. Future designs may eliminate the weir in favor of a small bed of
riprap at the discharge point to the sand filter chamber.
Maintenance of the filters was hampered by the lack of access to the
treatment chambers. Vertical sidewalls
were employed at all sites to preserve space, without an allowance for
equipment access. Future designs should
employ maintenance ramps to the sedimentation basin invert and filter bed.
Performance of the
filters was consistent with other published studies such as Glick, et.al.
(1998); however, it was interesting to note that the reduction of particulate
related constituents was independent of the influent concentration. This conclusion is attributed to the
filtering stage of this device that is highly effective in removing all but the
smallest particulate size fractions.
For particle size distributions found in urban storm water, the total
suspended solids concentration in the filter effluent is consistently about 8
mg/L. This finding is of value in cases
where a specific TSS effluent concentration is required. Nutrient removal was poor, with an increase
in effluent nitrate concentration but an overall net decrease in total
nitrogen.
Two types of vegetated controls were reviewed in the study, vegetated strips
and swales. Strips were constructed as
stand-alone BMPs as well as a pretreatment device for infiltration
trenches. A single type of vegetation
was used, salt grass, which is a plant native to California. It was selected since it is relatively low
growing, forms a dense matt and does not require irrigation.
Strips were designed using guidelines from WEF (1998) with a maximum
slope of 12 percent (prototype slopes were all less than 2%), and a length (in
the direction of flow) of 8 m.
Similarly, swales were designed following the guidelines from WEF with a
target minimum hydraulic residence time of 9 minutes, a maximum longitudinal
slope of 5 percent, a maximum velocity of 0.3 m/s and a maximum base width of
2.5 m. A literature review of these
design criteria concludes that they are based on few installations, and
virtually no work has been done to refine them.
One of the primary
problems with the current design guidelines is that there is no direct
consideration of the relationship between tributary area and treatment
area. The strips constructed in this
study had a tributary area to treatment area ratio of from 4 to 43. Similarly, the swales constructed in the
study had a ratio that varied from 13 to 53.
Guidelines specifying a minimum for the tributary area to treatment area
ratio are needed to assist the designer to achieve a performance benchmark
while using the available space efficiently. Swale design could benefit from
more rigorous guidance for depth and maximum flow velocity. Vegetated controls
have performance that equals or exceed most other BMPs, yet require little
maintenance and have a low capital and maintenance cost.
Two types of infiltration devices were reviewed as a part of the study,
infiltration basins and infiltration trenches.
A review of design criteria in the US showed that recommended in situ
soil infiltration rates varied greatly from about 5 mm/hr to about 100
mm/hr. A minimum in situ
infiltration rate of 7 mm/hr and a minimum separation to the season high
groundwater table of 0.6 meters was used in the study. The maximum ponding depth was 0.9 m for
basins, and basins and trenches were designed to completely empty the water
quality volume within 72 hours.
Studies have show that more than half of all infiltration devices fail
within the first five years of operation (Schueler et.al., 1992). This is generally the result of clogging of
the site soils, or due to high groundwater.
Of the four infiltration devices constructed as a part of this study,
two failed or did not perform at design level expectations. One of the infiltration trenches was
constructed in fractured sandstone. The
intrinsic permeability of the sandstone was very poor; however, the fractures
created sufficient permeability so as to meet the design requirements. Unfortunately, the fractures in the rock
were not homogeneous, and when the trench was constructed, far fewer fractures
on a relative basis (as compared to the in drill hole permeability test) were
present. This resulted in trench drain
times from a full condition of about 2 weeks.
The second location that failed was an infiltration basin. The groundwater at this location was
measured about 0.6 m from the basin invert during the soil permeability
testing. During construction, the
groundwater elevation rose to within 0.3 m of the basin invert. The design invert elevation was raised about
0.3 m during construction to compensate for the rise in the groundwater table. However, the groundwater table continued to
rise after construction was complete, at times nearly coinciding with the basin
invert. As a result, water often
remained in the basin several months following rain events.
Clearly, some of
the infiltration devices in this study were sited in marginal conditions. Since there are readily available
alternatives to infiltration, infiltration should only be used where conditions
are favorable. Highly permeable soils
will increase the risk of groundwater contamination. A portion of the study was designed to measure changes in groundwater
quality below the infiltration devices using lysimeters to obtain groundwater
samples. This portion of the study was
not successful due to the inability to obtain samples. Further study on the potential of
groundwater contamination from storm water is warranted.
One wet pond was
monitored as a part of the study. The
primary design criteria included a three to one ratio for the permanent pool to
water quality volume. Depth in the open
water areas was from 1.1 to 1.9 m with a 0.3 m bench around the pond perimeter
to promote vegetation growth and enhance public safety. Dry weather flow was intercepted from an
adjacent channel to sustain the permanent pool. The pond was sited upstream of a coastal estuary that is impaired
for nutrients.
A mass balance for constituents in and out of the pond was developed and
it was determined that the dry weather inflow was relatively high in nitrate
(about 15 mg/L as N) and phosphorus (about 2.2 mg/L). Prior to construction of the pond, these nutrients were being
contributed to the estuary on a year-round basis. This contribution was especially critical during the summer
months when additional daylight promoted more algal growth in the estuary, and
the associated low ambient oxygen levels.
The pond operation reduced each of these nutrients by about half, most
likely benefiting the receiving water beyond the treatment provided during
storm events.
Two primary research needs for pond design were identified at the
conclusion of the study. First, there
is a lack of definitive guidance for the ratio of permanent pond volume to
influent volume. The authors feel that
a permanent pool volume of twice the mean annual storm will provide good
results. The second research need is the requirement of perennial flow to
sustain the pond. This is a fairly
restrictive siting requirement, and the applicability of wet ponds could be
greatly expanded if storm water were used to initially fill the dead storage
area of the pond at the beginning of the wet season. Investigation is needed to determine if the water quality in the
pond would remain acceptable, if performance is comparable to the traditional
design, and if vector control becomes more problematic.
A primary part of
the study was concerned with tracking the costs of construction of the
devices. There are sufficient
references for the development of BMP construction cost associated with new
development or significant redevelopment, however, little documentation is
available concerning stand-alone BMP retrofit.
The results of the cost analysis show that stand-alone retrofit
construction cost is substantially greater than construction of BMPs with a
larger project. This is due to many
factors such as economy of scale, accommodation of existing operations at the
site and limited work area. Overall,
the costs of the devices ranged from a high of $ 3,472 (sand filter) to a low
of $246 (swale) per cubic meter of water treated. A premium for retrofit of about 34 percent over the cost of new
construction was estimated from the compiled data. Accordingly, storm water retrofit projects should be combined
with other capital improvement projects whenever possible for increased
economy.
Historically,
vectors such as mosquitoes, have received comparatively little consideration
when designing BMPs. Many devices
retain water for extended periods, or maintain standing water indefinitely (wet
pond, Delaware sand filter) creating a potential vector habitat. The devices in this study were designed to
impound water for a maximum of 72 hours, a span less than that required to
complete the mosquito breeding cycle.
The wet pond was stocked with mosquito fish and the Delaware filter was
treated with synthetic hormones. The US
has recently seen of proliferation of the West Nile virus, which is transmitted
through mosquitoes. Future BMP designs must limit the opportunities for
standing water and routine inspections should include an assessment of vector
breeding.
Analysis of the water quality data collected during the study indicated
that in many cases the traditional method of reporting performance as a percent
reduction in the influent concentration did not correctly convey the relative
performance of the BMPs. The problem
was primarily the result of differences in influent runoff quality among the
various sites. Devices that were
installed at park-and-ride lots, where the untreated runoff had relatively low
constituent concentrations resulted in a low calculated removal efficiency even
though the quality of the effluent was equal to that achieved with the same
device at another location.
Consequently, a methodology was developed using linear regression to
predict the expected effluent quality for each of the BMPs as if they were
subject to identical influent quality.
The study found that a comparison on this basis resulted in a more valid
assessment of the relative performance of the technologies.
Table 1 presents the expected effluent quality for total suspended
solids (TSS), total phosphorus, and total zinc that would be achieved if each
of the BMPs were subject to runoff with influent concentrations equal to that
observed on average for highway and maintenance stations during the study. Effective concentrations of zero are shown
for the infiltration devices, since there is no discharge to surface waters.
Table 1 Effluent Expected Concentrations for BMP
types
|
Device |
TSS
(Influent 114 mg/L) |
Total Phosphorus (Influent 0.38 mg/L) |
Total Zn
(Influent 355 ug/L) |
|
Austin Sand Filter |
7.8 |
0.16 |
50 |
|
Delaware Sand Filter |
16.2 |
0.34 |
24 |
|
EDB unlined |
36.1 |
0.24 |
139 |
|
Wet Basin |
11.8 |
0.54 |
37 |
|
Infiltration Basin |
0 |
0 |
0 |
|
Infiltration Trench |
0 |
0 |
0 |
|
Vegetated Swale |
58.9 |
0.62 |
96 |
|
Vegetated Strip |
27.6 |
0.86 |
79 |
A series of figures
were created for the devices ranked by life cycle cost from most to least
expensive and graphed against constituent concentration and load reduction. The
life-cycle costs include the expected maintenance cost estimated from the final
maintenance protocol for each device developed at the conclusion of the
study. One could reasonably expect that
those devices on the left side of the graph would have lower effluent
concentrations and greater load reduction since they have a higher capital
cost. As shown in the example for TSS in Figure 2, this is not always the case.
Error bars on the graph indicate the reliability of the estimated effluent
concentrations and load reductions. This uncertainty indicates the 90 percent
confidence interval of the estimate of the mean effluent concentration.

Figure 2 Predicted TSS
Effluent Concentration
Several of the BMPs in this study were found to
be inappropriate for the study sites due to poor constituent removal, excessive
complexity and cost, relatively high maintenance requirements or a combination
of these factors. The rejected BMPs
included the oil/water separator, drain inlet inserts, the multi-chambered
treatment train and the Stormfilterâ.
A family of performance graphs were developed
indicating constituent removal efficiency by device ranked by relative
life-cycle cost. The graphs were
generated from consistent influent constituent concentrations to allow their
application by the designer for any given set of conditions. These graphs are available from the authors
on request.
Acknowledgements: This research effort was funded by the
California Department of Transportation under Contract Nos. 43A0004A and
43A0051. Prime contractor for the study was RBF Consulting and monitoring and
operation of the tests sites were conducted by KLI and Brown and Caldwell and
Mactech.
LIST OF
REFERENCES
Glick,
Roger, Chang, George C., and Barrett, Michael E., 1998. “Monitoring and
Evaluation of Stormwater Quality Control Basins,” in Watershed Management:
Moving from Theory to Implementation. Denver, CO, May 3-6, 1998, pp 369 ‑
376.
Schueler, T.R., Kumble, P.A. and Heraty, M.A.,1992. “A Current Assessment of Urban Best Management Practices, Techniques for Reducing Non-point Source Pollution in the Coastal Zone,” Metropolitan Washington Council of Governments, Washington, D.C.
Water Environment Federation (WEF) and ASCE,
1998. “Urban Runoff Quality Management,” WEF Manual of Practice, No. 23,
ASCE Manual and Report on Engineering Practice No. 87.
Young, G.K. et al.,1996. Evaluation and Management of Highway Runoff Water Quality. Publication No. FHWA-PD-96-032, U.S. Department of Transportation, Federal Highway Administration, Office of Environmental and Planning.